www.acehomeinspections.netP.O. Box 1993 | |||
| 
       Customer  | |||
| 
       Home   | |||
| 
       Real Estate Agent  | |||
      
  | |||
      
  | |||
      
  | |||
 
![]() www.acehomeinspections.net P.O. Box 1993  | |
| 
       Customer  | |
| 
       Home   | |
This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the home.
This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.
WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING 
WALLS
| 2.1 | WALKWAYS, 
      DRIVEWAYS, LANDSCAPING, RETAINING WALLS  MINOR REPAIRS, (REFER TO REPORT PICTURES) 1,2-There is a fallen tree blocking the entire right side of the building. Recommend removal by a licensed contractor.  | 
PORCHES, DECKS, PATIOS, STEPS, STAIRS, RAILINGS, 
BANISTERS
| 3.2 | PORCHES, 
      DECKS, PATIOS, STEPS, STAIRS, RAILINGS, BANISTERS  MINOR REPAIRS, (REFER TO REPORT PICTURES) 1-There are two concrete sets of steps on the far left side of the property. One set has proper railings while the other does not. Proper railings are always recommended. (safety issue)  | 
EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, 
GUTTERS, ROOF, CHIMNEY
| 4.2 | EXTERIOR 
      DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY 
       MINOR REPAIRS, (REFER TO REPORT PICTURES) 1-One front window in Building E is broken and needs to be replaced.  | 
| 4.3 | EXTERIOR 
      DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY 
       MINOR REPAIRS, (REFER TO REPORT PICTURES) 1-All rear window trim boards are wood. Some of them are deteriorated and will need to be replace and recommend painting all exterior wood on all buildings.  | 
| 4.4 | EXTERIOR 
      DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY 
       MINOR REPAIRS, (REFER TO REPORT PICTURES) 1-Overall roof covering appeared adequate and is estimated to be from 12 to 15 years old. Some of the rear bottom edge left shingles appear aged. The small sloped roofs over the three rear porches need to have new flashing where they attach to the siding.  | 
| 4.5 | EXTERIOR 
      DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY 
       MORE THAN MINOR REPAIRS, (REFER TO REPORT PICTURES) 1,2-Sections of vinyl and asbestos siding are missing on the right rear corner of the building. Immediate repairs by a licensed siding contractor are recommended.  | 
KITCHEN, BATHROOMS, ALL OTHER INTERIOR 
ROOMS
| 6.0 | KITCHEN, 
      BATHROOMS, ALL OTHER INTERIOR ROOMS (unit 1)  MINOR REPAIRS, (REFER TO REPORT PICTURES) 1-Rear door has a broken window pane that needs to be replaced. 2-The water heater needs a PT valve discharge pipe installed within three inches of the floor. Water heater is only 8 years old and should most likely last another 10 to 12 years. This is good! 3-The kitchen sink faucet is missing. 4-The bathroom commode is missing. 5,6,7-The bathroom tub and sink faucets are missing and tub needs to be disinfected. 8-Refrigerator has graffiti written all over it and is very dirty with decayed food. About 6 or 7 of the units refrigerators have not been cleaned and have decayed food.  | 
| 6.2 | KITCHEN, 
      BATHROOMS, ALL OTHER INTERIOR ROOMS (unit 2)  MORE THAN MINOR REPAIRS, (REFER TO REPORT PICTURES) 1,2,3,4,5,6,7,8,9,10,11,12-Many structural changes have been made to unit 2. The walls between the bedrooms and the living room wall have been removed and made into one large room that also encompasses the center closet and hallway. Wood beams have been added along the ceiling supported by rustic logs. The original windows have been replaced with fixed panes surrounded by rustic logs. Water is seeping in around the rear and side windows and the fixed glass panes are cracked. The original bathroom tub and commode have been replaced. The original floor furnace has been replaced with an above floor level gas heater surrounded by rocks. The kitchen has been converted into a laundry room. A hallway opening has been installed where one can enter into unit 1 on the left side. It does not appear that any modifications were made to unit 1 other than the ability to walk into both units through the new center hallway. Overall it appears that none of the modifications started have been fully completed. Unit 2 is in complete disarray with numerous items started but none finished. Major reconstruction will need to be done in order to transfer unit 2 back into a functional and liveable unit. 13,14-The electrical panel cover needs to be installed. (safety issue) The panel interior appeared adequate and free of moisture discoloration and deterioration. 15-Many electrical outlets and switches need appropriate covers. Recommend a licensed electrical contractor further inspect all wiring and make all necessary corrections. (safety issue) 16,17-The original central gas furnace has been replaced. Unknown as to safety and functionality of system. Complete removal and installation of a standard gas central furnace in the crawlspace is recommended by a licensed heating and air contractor.  | 
| 6.4 | KITCHEN, 
      BATHROOMS, ALL OTHER INTERIOR ROOMS (unit 3)  MINOR REPAIRS, (REFER TO REPORT PICTURES) 1-The vinyl flooring along the tub is peeling up from moisture deterioration and needs to be secured/repaired and caulked. 2-Hallway smoke alarm needs to be replaced. Smoke alarms are always recommended in all hallways and bedrooms in all units. 3,4-Water heater is aged and needs an appropriate PT valve discharge pipe installed within three inches of the floor. Expect to replace this unit in near future. Operation could not be tested because all utilities are turned off.  | 
| 6.6 | KITCHEN, 
      BATHROOMS, ALL OTHER INTERIOR ROOMS (unit 4)  MINOR REPAIRS, (REFER TO REPORT PICTURES) 1-Living room 110 volt receptacle is aged and needs to be replaced. (safety issue) 2-Water heater is aged and needs and needs a PT valve discharge pie installed within three inches of the floor. Unit could not be tested because the utilities are turned off. 3-Kitchen counter covering is peeling up and needs to be secured. Recommend a piece of metal trim. 4,5-Wood floor decking around commode is deteriorated and needs to be replaced. 6-One door knob needs to be replaced. 7-One bedroom outlet needs a proper cover. (safety issue)  | 
Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.
| 1.0 | GENERAL INFORMATION 
       Comments: FOR YOUR INFORMATION None of the four units have the electricity, gas, and water on. ACE Home Inspections, LLC is not responsible for problems such as hidden water leaks and non-working gas appliances uncovered after all utilities have been turned on in any of the vacant units. Be sure to monitor all areas for water leaks upon turning water on to any vacant unit.  | 
| WALKWAYS: CONCRETE  | 
    DRIVEWAYS: CONCRETE/ASPHALT  | 
    RETAINING WALLS: NONE  | 
| LANDSCAPING: RELATIVELY LEVEL PROPERTY  | 
    LANDSCAPING: OPEN FRONT YARD  | 
    LANDSCAPING: TALLS TREES SIDES AND REAR  | 
| 2.0 | WALKWAYS, DRIVEWAYS, 
      LANDSCAPING, RETAINING WALLS 
 1,2-Driveway and parking area asphalt has some cracks, and some areas are deteriorated or missing. Some areas are part asphalt and some gravel.  | 
| 2.1 | WALKWAYS, DRIVEWAYS, 
      LANDSCAPING, RETAINING WALLS 
 1,2-There is a fallen tree blocking the entire right side of the building. Recommend removal by a licensed contractor.  | 
| 2.2 | WALKWAYS, DRIVEWAYS, PATIOS, 
      LANDSCAPING, RETAINING WALLS (Visible condition. Checking for proper water 
      runoff away from the house, the landscape for presence of holes, sunken 
      areas, bald spots, eroding areas, and tripping hazards, trees and 
      vegetation clearances, and drainage weep holes or drains at the base of 
      retaining walls.)  Comments: INSPECTED  | 
| PORCHES: FRONT IS SMALL HIP EACH REAR IS SMALL SLOPED  | 
    PORCH FOUNDATION: CONCRETE BLOCK CONCRETE SLAB  | 
    PORCH ROOF: EACH HAS OWN SMALL SLOPED WOOD CONSTRUCTION  | 
| COLUMNS: DESIGNER METAL TUBING  | 
    STEPS: 1 SET FRONT CONCRETE 3 SETS REAR CONCRETE  | 
    STAIRWAYS: 1 COMMON FRONT STAIRS 1 SPLIT REAR STAIRS  | 
| STAIRWAY INFO: ALL 4 APTS USE FRONT UPPER 2 APT USE REAR  | 
    STAIRWAY INFO: WOOD STAIRS WOOD RAILINGS PLASTERBOARD WALLS PLASTERBOARD CEILING  | 
    STAIRWAY INFO: FRONT ENTRY AREA ONE MIDDLE LANDING UPPER ENTRY AREA  | 
| 3.0 | PORCHES, DECKS, PATIOS, 
      STEPS, STAIRS, RAILINGS, BANISTERS 
 1,2-Rear shared stairway for the upper floor units appears adequate with a proper railing. This is good! Unknown if lighting works since power is off to all building units. All four units are unoccupied with all utilities off.  | 
| 3.1 | PORCHES, DECKS, PATIOS, 
      STEPS, STAIRS, RAILINGS, BANISTERS 
 1-Rear porch banisters need to be painted.  | 
| 3.2 | PORCHES, DECKS, PATIOS, 
      STEPS, STAIRS, RAILINGS, BANISTERS 
 1-There are two concrete sets of steps on the far left side of the property. One set has proper railings while the other does not. Proper railings are always recommended. (safety issue)  | 
| 3.3 | PORCH (Visible condition of 
      roof, eaves, gutters, attic, ventilation, columns, foundation, floor, 
      coverings, storage closets.)  Comments: INSPECTED  | 
| 3.4 | PORCH (Visible condition and 
      operation of doors, lights, switches, and outlets.)  Comments: INSPECTED  | 
| 3.5 | COMMON HALLWAYS AND CORRIDORS 
      (Visible condition and operation of windows, doors, floors, cabinets, 
      lights, switches, outlets, heating, cooling.)  Comments: INSPECTED  | 
| 3.6 | STOOPS, STEPS, STAIRS, 
      BANISTERS, AND RAILINGS (Visible condition. Checking for potential 
      tripping hazards from variations in step riser heights, narrow tread 
      steps, unlevel steps or steep stairs. Checking for adequate 
      headroom.)  Comments: INSPECTED  | 
| 3.7 | SPACINGS BETWEEN ANY TWO 
      RAILING BANISTERS OF 4 TO 5 INCHES OR LESS (Safety issue for 
      children.)  Comments: INSPECTED  | 
| EXTERIOR DOORS: UNIT FRONT ENTRY DOOR UNIT REAR ENTRY DOOR  | 
    EXTERIOR DOORS: FRONT STAIRWAY ENTRY DOOR REAR STAIRWAY ENTRY DOOR  | 
    EXTERIOR DOORS: WOOD PANELED  | 
| INTERIOR DOORS: DEADBOLTS  | 
    HOUSE WINDOWS: ALUMINUM ALUMINUM SASHES  | 
    HOUSE WINDOW TYPE: SINGLE-HUNG  | 
| HOUSE WINDOW TYPE: SINGLE PANE  | 
    SIDING MATERIAL: VINYL FRONT ASBESTOS TILE REAR  | 
    SIDING STYLE: LAP  | 
| GUTTER MATERIAL: ALUMINUM  | 
    FOUNDATION MATERIAL: CONCRETE BLOCK  | 
    SOFFIT/FASCIA 
      MATERIAL: WOOD  | 
| VIEWED ROOF FROM: GROUND (binoculars) VIEWED FROM SECOND FLOOR  | 
    ROOF TYPE: GABLE  | 
    ROOF COVERING: FIBERGLASS ASPHALT SHINGLES  | 
| LAYERS: TWO  | 
    ESTIMATED ROOF AGE: 12 TO 15 YEARS  | 
    ROOF VENTILATION: GABLE VENTS SOFFIT VENTS  | 
| 4.0 | EXTERIOR DOORS, WINDOWS, 
      SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY 
 1,2-Front siding, window trim, and soffit and fascia is vinyl and aluminum, which is low maintenance. The rear side of all buildings are the original asbestos type lap shingles.  | 
| 4.1 | EXTERIOR DOORS, WINDOWS, 
      SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY 
 1-Recommend a small hole in soil against front wall be built up with additional soil. The crawlspace areas in all buildings were relatively dry and free of standing water and moisture, however it is always recommended that all soil against the foundation be properly sloped down and away.  | 
| 4.2 | EXTERIOR DOORS, WINDOWS, 
      SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY 
 1-One front window in Building E is broken and needs to be replaced.  | 
| 4.3 | EXTERIOR DOORS, WINDOWS, 
      SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY 
 1-All rear window trim boards are wood. Some of them are deteriorated and will need to be replace and recommend painting all exterior wood on all buildings.  | 
| 4.4 | EXTERIOR DOORS, WINDOWS, 
      SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY 
 1-Overall roof covering appeared adequate and is estimated to be from 12 to 15 years old. Some of the rear bottom edge left shingles appear aged. The small sloped roofs over the three rear porches need to have new flashing where they attach to the siding.  | 
| 4.5 | EXTERIOR DOORS, WINDOWS, 
      SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY 
 1,2-Sections of vinyl and asbestos siding are missing on the right rear corner of the building. Immediate repairs by a licensed siding contractor are recommended.  | 
| 4.6 | WINDOWS, SHUTTERS AND AWNINGS 
      (Visible condition and checking for the presence and functionality of 
      window flashing and operation of windows and window locks.) 
       Comments: INSPECTED  | 
| 4.7 | ENTRY DOORS, STORM DOORS, 
      SECURITY DOORS, AND DOORBELL (Visible condition and operation, checking 
      hardware, locks, coverings, frame, trim, weatherstripping, presence of 
      deadbolts on all exterior doors, proper locking, opening, and closing of 
      sliding glass doors, and the presence of a security dead-pin in all 
      sliding glass doors.)  Comments: INSPECTED  | 
| 4.8 | FOUNDATION WALLS AND MORTAR 
      JOINTS (Visible condition, checking for cracked, crumbled, loose, missing, 
      eroded areas, or large gaps)  Comments: INSPECTED  | 
| 4.9 | EXTERIOR WALL COVERINGS, 
      FLASHING,TRIM, AND CAULKING (Visible condition. A wall flashing is defined 
      as a material used around angles or junctions on exterior walls to prevent 
      water leakage.)  Comments: INSPECTED  | 
| 4.10 | HOUSE FRAMING (Visible 
      condition, checking for any cracks developing outside of the house, cracks 
      between a chimney and the exterior wall or any cracks running outward at 
      an angle from the upper corners of windows and door frames.) 
       Comments: INSPECTED  | 
| 4.11 | OUTSIDE ACCESS TO HOUSE IS 
      RODENT PROOF  Comments: INSPECTED  | 
| 4.12 | ROOF COVERING (Visible 
      condition. Checking roof penetrations such as, roof vents, ridge vents, 
      wind turbines, soffit vents, gable vents, chimneys, furnace flues, water 
      heater flues, plumbing vents, skylights and any other penetrations. 
      Checking flashings which are used to seal around roof penetrations and 
      intersections. Checking rain caps on chimneys and flues.)  Comments: INSPECTED  | 
| 4.13 | SOFFIT, FASCIA, EAVES, 
      GUTTERS, DOWNSPOUTS (Visible condition. Checking if gutters are provided 
      where necessary, including porches, flat roofs, and dormers. Checking 
      whether splasblocks are in place if underground piping is not used for 
      rain gutter drainage.)  Comments: INSPECTED  | 
| ROOF STRUCTURE: 2 x 6 WOOD RAFTERS PLYWOOD ROOF DECKING PURLIN BRACING BOARDS  | 
    CEILING STRUCTURE: 2 x 6 WOOD JOISTS  | 
    INSULATION TYPE: BATT FIBERGLASS  | 
| INSULATION INCHES: 3 INCHES  | 
    R- VALUE: R-11  | 
    ACCESS LOCATED IN: HALLWAY SCUTTLE HOLE  | 
| RAFTER SPACING: 24 INCHES  | 
    JOIST SPACING: 16 INCHES  | 
    ATTIC INFO: NO DECKING FOR STORAGE  | 
| 5.0 | ATTIC, ROOF INTERIOR 
      
 1,2,3,4,5,6,7,8-The majority of wood members throughout the attic were relatively free of visible moisture discoloration and deterioration. The roof decking around most of the penetrations have some discoloration and were poked and found to still be relatively structurally adequate. These, most likely, were previous leaks that were fixed when the last roof covering was installed. Firestopping around flues appeared adequate. All areas were dry to the touch at the time of the inspection. The discolored areas of roof decking will need to be addressed the next time the roof covering is replaced.  | 
| 5.1 | ATTIC, ROOF INTERIOR 
      
 1-Fiberglass insulation was observed in all attic areas. R-value or resistance to heat loss is estimated to be around R-11. R-30 is always recommended for optimum efficiency which would require installing an additional 7 to 10 inches of insulation.  | 
| 5.2 | ATTIC, ROOF INTERIOR 
      
 1-Recommend proper screening on both gable vents to keep small animals from entering the attic. 2-There is a door being stored in the attic above unit 3.  | 
| 5.3 | ATTIC, ROOF INTERIOR 
      
 1-The upgraded central gas furnaces exhaust flue piping for both upstairs units have been adequately connected into the existing flues. 2-The water heater flue pipes need to be monitored for leakage when the gas has been turned on and the unit is in operation. They appear to be aged and there is a possibility they may be leaking at the connection joint.  | 
| 5.4 | ATTIC, ROOF INTERIOR (Visible 
      condition. Checking attic insulation, exposed wiring, lights and water 
      pipes. Checking to see that all attic areas are accessible, all exposed 
      sections of chimney in attic are free of soot and creosote leakage, that 
      soffit vents are not covered with insulation, and attic ventilation vent 
      screening which keeps animals out)  Comments: INSPECTED  | 
| 5.5 | GAS FLUE AND CHIMNEY 
      FIRESTOPPING (Visible condition. Firestopping refers to size of the hole 
      made in the ceiling and roof so as to maintain the proper clearance from a 
      hot metal flue pipe or chimney brick.)  Comments: INSPECTED  | 
| 5.6 | DO ALL FLUES AND VENTS 
      PRESENT IN ATTIC TERMINATE TO THE EXTERIOR (Water heater flue, furnace 
      flue, metal chimney flue, plumbing vents, bathroom fan vents, range hood 
      vent, dryer vent, etc...)  Comments: INSPECTED  | 
| 5.7 | RAFTERS, DECKING, JOISTS OR 
      TRUSSES (Visible condition. Check for rafters pulling away from ridge 
      board, rot, cracks, splits, cut, altered or missing supports.) 
       Comments: INSPECTED  | 
| 5.8 | IS ATTIC FREE OF VISIBLE ROOF 
      LEAKS OR DETERIORATION (Flashing refers to materials, usually metal, that 
      join parts of the house to the roof. Common places where roof leaks occur 
      are flashings around chimneys, metal gas flues, plumbing vents, turbines, 
      dormers, valleys, or any other roof penetrations or intersections.) 
       Comments: INSPECTED  | 
| 5.9 | IS ATTIC FREE OF VISIBLE 
      CONDENSATION OR MOISTURE DAMAGE DUE TO IMPROPER VENTILATION (Often what 
      appears to be a leak is in fact condensation, and a sign of inadequate 
      ventilation. Proper attic ventilation reduces heat in summer and prevents 
      condensation in winter. It allows air to carry off water vapor before it 
      can condense and cause moisture damage.)  Comments: INSPECTED  | 
| 5.10 | INSTALLED MECHANICAL 
      VENTILATION SYSTEMS (Visible condition and operation of power ventilators 
      and fans)  Comments: INSPECTED  | 
| UTILITIES (unit 1): NO POWER/GAS/WATER UNIT IS VACANT  | 
    UTILITIES (unit 2): NO POWER/GAS/ELECTRICITY UNIT IS VACANT  | 
    UTILITIES (unit 3): NO POWER/GAS/ELECTRICITY UNIT IS VACANT  | 
| UTILITIES (unit 4): NO POWER/GAS/ELECTRICITY UNIT IS VACANT  | 
    CABINETRY: CUSTOM-MADE TYPE  | 
    CABINETRY: ALL SOLID WOOD  | 
| KITCHEN FLOOR: LINOLEUM  | 
    KITCHEN COUNTERTOP: METAL SINK CABINET TOP  | 
    KITCHEN SINK: SINGLE BASIN  | 
| DRAIN PLUMBING: MIX OF PVC AND METAL PIPING  | 
    WATER CONNECTION: GRAY PLASTIC TUBING  | 
    STOVE ENERGY: NATURAL GAS  | 
| REFRIGERATOR (unit 
      1): HOTPOINT  | 
    REFRIGERATOR (unit 
      2): NONE  | 
    REFRIGERATOR (unit 
      3): HOTPOINT  | 
| REFRIGERATOR (unit 
      4): MAGIC CHEF  | 
    WATER HEATER DATE (unit 
      1): US CRAFTMASTER 06/1997  | 
    WATER HEATER DATE (unit 
      2): WHIRLPOOL 40 GAL 12/2002  | 
| WATER HEATER DATE (unit 
      3): OLD UNKNOWN  | 
    WATER HEATER DATE (unit 
      4): OLD UNKNOWN  | 
    ELECTRIC PANEL INFO (unit 
      1): SIEMENS ITE 125 AMP CIRCUIT BREAKERS  | 
| ELECTRIC PANEL INFO (unit 
      2): GE 125 AMP CIRCUIT BREAKERS  | 
    ELECTRIC PANEL INFO (unit 
      3): SYLVANIA 100 AMP CHALLENGER BREAKERS  | 
    ELECTRIC PANEL INFO (unit 
      4): FUSE TYPE 100 AMPS GENERAL SWITCH  | 
| INTERIOR ROOMS: 2 BEDROOMS LIVING ROOM HALLWAY KITCHEN BATHROOM CENTER CLOSET  | 
    WALL/CEILING 
      MATERIAL: PLASTERBOARD  | 
    FLOOR MATERIALS: LINOLEUM HARDWOOD T&G CARPET  | 
| HEATING UNIT INFO (unit 
      1): ORIGINAL GAS FLOOR FURNACE UPGRADED UNIT LOCATED IN CRAWLSPACE  | 
    HEATING UNIT INFO (unit 
      3): GAS CENTRAL WALL FURNACE UPGRADED CLOSET UNIT HEIL 2-PORT UNIT 50000 BTU MADE 1998  | |
| HEATING UNIT INFO (unit 
      4): GAS CENTRAL WALL FURNACE UPGRADED CLOSET UNIT RHEEM 2-PORT UNIT 45000 BTU MADE 04/1986  | 
| 6.0 | KITCHEN, BATHROOMS, ALL OTHER 
      INTERIOR ROOMS (unit 1) 
 1-Rear door has a broken window pane that needs to be replaced. 2-The water heater needs a PT valve discharge pipe installed within three inches of the floor. Water heater is only 8 years old and should most likely last another 10 to 12 years. This is good! 3-The kitchen sink faucet is missing. 4-The bathroom commode is missing. 5,6,7-The bathroom tub and sink faucets are missing and tub needs to be disinfected. 8-Refrigerator has graffiti written all over it and is very dirty with decayed food. About 6 or 7 of the units refrigerators have not been cleaned and have decayed food.  | 
| 6.1 | KITCHEN, BATHROOMS, ALL OTHER 
      INTERIOR ROOMS (unit 1) 
 1-Washer connections are located under the kitchen metal sink cabinet. 2,3-The electrical panel appeared adequate and free of moisture discoloration and deterioration. 4-Kitchen view. 5-Window unit could be tested because all utilizes are turned off. 6,7,8-All walls, ceilings, and doors have been covered with graffiti. Several coats of paint is recommended. (cosmetic issue) 9-The unit has a central gas floor furnace. See section 10 for view of unit from the crawlspace. 10-Recommend all window sills be painted.  | 
| 6.2 | KITCHEN, BATHROOMS, ALL OTHER 
      INTERIOR ROOMS (unit 2) 
 1,2,3,4,5,6,7,8,9,10,11,12-Many structural changes have been made to unit 2. The walls between the bedrooms and the living room wall have been removed and made into one large room that also encompasses the center closet and hallway. Wood beams have been added along the ceiling supported by rustic logs. The original windows have been replaced with fixed panes surrounded by rustic logs. Water is seeping in around the rear and side windows and the fixed glass panes are cracked. The original bathroom tub and commode have been replaced. The original floor furnace has been replaced with an above floor level gas heater surrounded by rocks. The kitchen has been converted into a laundry room. A hallway opening has been installed where one can enter into unit 1 on the left side. It does not appear that any modifications were made to unit 1 other than the ability to walk into both units through the new center hallway. Overall it appears that none of the modifications started have been fully completed. Unit 2 is in complete disarray with numerous items started but none finished. Major reconstruction will need to be done in order to transfer unit 2 back into a functional and liveable unit. 13,14-The electrical panel cover needs to be installed. (safety issue) The panel interior appeared adequate and free of moisture discoloration and deterioration. 15-Many electrical outlets and switches need appropriate covers. Recommend a licensed electrical contractor further inspect all wiring and make all necessary corrections. (safety issue) 16,17-The original central gas furnace has been replaced. Unknown as to safety and functionality of system. Complete removal and installation of a standard gas central furnace in the crawlspace is recommended by a licensed heating and air contractor.  | 
| 6.3 | KITCHEN, BATHROOMS, ALL OTHER 
      INTERIOR ROOMS (unit 2) 
 1-Water heater appeared adequate and has been changed from a gas unit to an electric unit and is only 2 years old. The unit could not be tested because all building utilities are turned off. 2,3-Views of original kitchen which is now a laundry room. 4,5-View of new center hallway that allows one to walk from unit 2 to unit 1. This like all other modifications was never completed. 6-Unit 1 door states E1 and E2 are now one unit.  | 
| 6.4 | KITCHEN, BATHROOMS, ALL OTHER 
      INTERIOR ROOMS (unit 3) 
 1-The vinyl flooring along the tub is peeling up from moisture deterioration and needs to be secured/repaired and caulked. 2-Hallway smoke alarm needs to be replaced. Smoke alarms are always recommended in all hallways and bedrooms in all units. 3,4-Water heater is aged and needs an appropriate PT valve discharge pipe installed within three inches of the floor. Expect to replace this unit in near future. Operation could not be tested because all utilities are turned off.  | 
| 6.5 | KITCHEN, BATHROOMS, ALL OTHER 
      INTERIOR ROOMS (unit 3) 
 1-Unit 3 has a window unit but could not be tested. 2-Several holes in living room wall will need to be patched. 3-Hardwood T&G flooring appears adequate. 4-Many walls throughout all units have cracked and peeled paint. This is considered normal for units like these that have sat vacant for extended periods of time with no utilities. The paint is aged and needs to be scraped and painted over. (cosmetic issue) 5,6-The original central gas wall furnace has been upgraded to a closet unit which is only seven years old with years of useful life. All vent piping appears adequate. This is good! 7-Kitchen view. 8,9-The electrical panel appeared adequate and free of moisture discoloration and deterioration. 10-3E!  | 
| 6.6 | KITCHEN, BATHROOMS, ALL OTHER 
      INTERIOR ROOMS (unit 4) 
 1-Living room 110 volt receptacle is aged and needs to be replaced. (safety issue) 2-Water heater is aged and needs and needs a PT valve discharge pie installed within three inches of the floor. Unit could not be tested because the utilities are turned off. 3-Kitchen counter covering is peeling up and needs to be secured. Recommend a piece of metal trim. 4,5-Wood floor decking around commode is deteriorated and needs to be replaced. 6-One door knob needs to be replaced. 7-One bedroom outlet needs a proper cover. (safety issue)  | 
| 6.7 | KITCHEN, BATHROOMS, ALL OTHER 
      INTERIOR ROOMS (unit 4) 
 1-Bedroom wall is rough. (cosmetic issue) 2,3-Recommend all wood window sills be painted. 4-Kitchen view. 5-Most metal sink basins are blemished and discolored but are still adequate. 6-Unit has washer connections under the kitchen sink. 7-Bathroom sink metal drain piping is corroded and could start leaking in near future. Replacement is recommended in near future. 8,9-The original central gas wall unit has been upgraded with a closet unit. The unit is 19 years old and could not be tested because all utilities are off. 10-All units have metal exterior and interior door frames. This is good! 11-4E!  | 
| 6.8 | KITCHEN (Visible condition of 
      ceiling, walls, cabinets, shelving, countertops, plumbing. Checking that 
      all outlets within six feet of sink have GFCI protection, and there are 
      separate water shut-off valves for faucet, dishwasher, and 
      ice-maker.)  Comments: INSPECTED  | 
| 6.9 | KITCHEN (Visible condition 
      and operation of windows, doors, floor, cabinet doors, drawers, lights, 
      switches, outlets, sink, faucet, spray nozzle and all appliances staying 
      with house: range, oven, microwave, vent hood, dishwasher, disposal, 
      refrigerator or any other appliances. Checking that sink and dishwasher 
      drain properly, and hot and cold water pressure, volume, and temperature 
      are adequate.)  Comments: INSPECTED  | 
| 6.10 | RANGE HOOD VENTING SYSTEM (If 
      range hood is nonvented type, is there a clean charcoal or aluminum filter 
      in place. A nonvented hood is for filtering odors and grease vapors and 
      will not remove heat or steam like a vented range hood. A non-vented range 
      hood is identified by louvers on the front of the hood and does not vent 
      to exterior as a vented hood does.)  Comments: INSPECTED  | 
| 6.11 | ARE FAUCETS FREE OF HAMMERING 
      AND VIBRATING NOISES WHEN TURNED ON/OFF RAPIDLY (This occurs when water 
      flowing in the pipe comes to an abrupt stop, introducing shock and 
      vibrations that can damage pipes or fittings. It is caused by improper 
      sized pipes and can be fixed with an air chamber or antiknock coil which 
      provides an air cushion to absorb shock.)  Comments: INSPECTED  | 
| 6.12 | DOES SINK DRAIN INTO A P-TRAP 
      UNDER THE SINK (A trap is needed to provide a water seal that blocks sewer 
      gases from seeping back into house. Some homes still have S-type traps 
      that do not always vent properly. If a sucking and gurgling noise occurs 
      after almost all the water has drained, the water seal has been lost. All 
      S-traps should be converted to P-traps.)  Comments: INSPECTED  | 
| 6.13 | DOES SINK HAVE AN AIR GAP TO 
      PREVENT BACK SIPHONAGE (Simply speaking, the air gap prevents the dirty 
      sink water from being sucked back into the clean water supply pipes 
      through the end of the faucet if the sink should overflow. There should be 
      a gap of at least 1 inch between the end of the faucet where the water 
      exits and the flood rim of the sink.)  Comments: INSPECTED  | 
| 6.14 | IS THERE A GAS SHUT-OFF VALVE 
      AND DRIP LEG OR IN-LINE CLEANER (A drip leg or dirt pocket is a short 
      capped off pipe added into gas line serving as a collection area for 
      sediment to reduce the chance of clogged valves or burners.) 
       Comments: INSPECTED  | 
| 6.15 | INTERIOR ROOMS (Visible 
      condition of ceilings and walls.)  Comments: INSPECTED  | 
| 6.16 | INTERIOR ROOMS (Visible 
      condition and operation of windows, doors, floors, lights, switches, 
      outlets)  Comments: INSPECTED  | 
| 6.17 | BATHROOM (Visible condition 
      of ceiling, walls, cabinets, countertops, and caulking.)  Comments: INSPECTED  | 
| 6.18 | BATHROOM (Visible condition 
      and operation of windows, doors, floor, cabinet doors, drawers, exhaust 
      fans, lights, switches, outlets, sinks, tubs, showers, and commodes. 
      Checking presence of cut-off valves for faucets and commodes, proper 
      draining of sinks, tubs, showers and commodes, use of P-traps and not old 
      S-traps, proper air-gap for sinks, tubs, and hand-held shower wands to 
      prevent back siphonage, faucets for improper hammering and vibrating 
      noises when turned on/off rapidly, adequacy of hot and cold water 
      pressure, volume, and temperature, exhaust fans for proper venting to 
      building exterior and outlet GFCI protection.)  Comments: INSPECTED  | 
| PLUMBING SUPPLY: COPPER PVC  | 
    DISTRIBUTION: COPPER PVC  | 
    PLUMBING WASTE: METAL PIPE  | 
| WASTE SYSTEM: UNKNOWN  | 
    WATER SOURCE: PUBLIC  | 
    WATER CUT-OFF: AT STREET  | 
| WATER HEATER POWER 
      SOURCE: NATURAL GAS  | 
    WATER HEATER 
      LOCATION: KITCHEN  | 
    CAPACITY: 30 - 40 GALLONS  | 
| 7.0 | PLUMBING SYSTEM 
 1-All 20 units have individual water meters. There are ten located along the front right beside the road and ten more along the rear left beside the road.  | 
| 7.1 | WATER HEATER, PTV - PRESSURE 
      TEMPERATURE VALVE, PTV DRAIN PIPING (Visible condition. Checking presence 
      of a drain pan under unit if installed in attic or room over a living 
      area, and presence of a cold water inlet water cut-off valve.) 
       Comments: INSPECTED  | 
| 7.2 | FLUE PIPE AND VENTING 
      (Visible condition checking pipe rise, diameter, junction fit, screws, and 
      clearances. A properly vented gas system exhausts combustion products to 
      exterior and provides adequate oxygen for combustion.)  Comments: INSPECTED  | 
| 7.3 | COMBUSTION AIR SUPPLY 
      (Combustion is a chemical reaction that occurs when fuel gases combine 
      with oxygen and ignite. Visual inspection of flame characteristics is a 
      good indicator of air/gas mixture problems that cause incomplete 
      combustion.)  Comments: INSPECTED  | 
| 7.4 | IF FLUE PIPE GOES TO FURNACE 
      FLUE, IS IT ON TOP (If both the water heater and furnace go into the same 
      chimney sleeve, then the furnace must be on the bottom because it has most 
      BTU's and makes the draft.)  Comments: INSPECTED  | 
| 7.5 | WAS GAS WATER HEATER AREA 
      CHECKED WITH SNIFFER AND FOUND FREE OF LEAKS  Comments: INSPECTED  | 
| 7.6 | EXPOSED INTERIOR WATER PIPING 
      (Visible condition, looking for leaks, corrosion, sagging sections, and 
      valves where it enters house and stops at the point where it enters rooms 
      where it then will be described in each rooms description in this 
      report.)  Comments: INSPECTED  | 
| 7.7 | EXTERIOR HOSE FAUCETS, WATER 
      PRESSURE, WATER VOLUME, WATER DRAINS (Visible condition and operation. 
      Checking for presence of faucet backflow preventers.)  Comments: INSPECTED  | 
| 7.8 | CLOTHES WASHER WATER 
      CONNECTIONS, DRAIN PIPE, AND HOSES (Visible condition.)  Comments: INSPECTED  | 
| 7.9 | ELECTRIC CLOTHES DRYER OUTLET 
      OR GAS CLOTHES DRYER CONNECTION (Visible condition. Checking dryer exhaust 
      vent for exterior building termination and exterior cover with functional 
      flap.)  Comments: INSPECTED  | 
| SERVICE DROP TO 
      HOUSE: ABOVE GROUND  | 
    SERVICE DROP TO 
      HOUSE: USES A DRIP LOOP  | 
    SERVICE DROP TO 
      HOUSE: ATTACHES TO SIDING  | 
| MAIN PANEL TYPE: FUSES CIRCUIT BREAKERS  | 
    MAIN PANEL LOCATION: KITCHEN  | 
    15 AND 20 AMP CIRCUIT 
      TYPE: ROMEX WIRING  | 
| 8.0 | ELECTRICAL SYSTEM 
 1-There are only three occupied units, 1B, 2B, and 2D. All unoccupied units have had their electric meters removed.  | 
| 8.1 | EXTERIOR LIGHTS, SWITCHES, 
      OUTLETS (Visible condition and operation)  Comments: INSPECTED  | 
| 8.2 | SERVICE ENTRANCE CABLE 
      (Visible condition of cable, splices, house connection, porcelain 
      insulators, mast, masthead or gooseneck, conduit and if limbs or vines are 
      in the way. Service is run aerially overhead or buried underground. The 
      home owner's responsibility starts after cable splice where aerial feed is 
      connected to the house, and for a buried feed at the meter.) 
       Comments: INSPECTED  | 
| 8.3 | METER BASE TO PANEL (Visible 
      condition of base, how its attached to house, all cables and connectors, 
      look for illegal wire taps running to another panel or device which could 
      severely overload the service utility drop and meter base, and does meter 
      base amp rating closely match the fuse or circuit breaker panel amp 
      rating.)  Comments: INSPECTED  | 
| 8.4 | PANELS, FUSE BOXES, AND 
      SUB-PANELS (Visible condition. Checking panels for proper circuit or fuse 
      labeling, all circuit breakers same brand name as panel, one main breaker 
      or disconnect that cuts all power to house. Check that all wires to 
      single-pole breakers are colored black and not white.)  Comments: INSPECTED  | 
| 8.5 | ELECTRICAL SYSTEM GROUND 
      (Visible condition. A ground wire bleeds stray voltages to ground and 
      current should not flow continuously in this wire. A ground wire from the 
      neutral/grounding bus bar in main panel runs to a grounding electrode or 
      rod. There should also be a ground wire from the main panel 
      neutral/grounding bus bar to metal water pipes. Water pipes should be 
      voltage free. Check water pipes for presence of voltage.)  Comments: INSPECTED  | 
| 8.6 | PANEL BONDING STRAP (Visible 
      condition. A bonding strap or panel bond, is required in every main panel 
      to connect the neutral/grounding bus bar to the panel frame so that the 
      metal panel can't shock you if a live wire touches it.)  Comments: INSPECTED  | 
| 8.7 | ARE PANEL FILLER PLATES IN 
      PLACE WITH NONE MISSING (Filler plates are little knockouts that are 
      removed from panel front if breakers are installed. If no breaker was 
      installed, this open spot is where someone could reach in and touch a hot 
      spot.)  Comments: INSPECTED  | 
| 8.8 | ARE LOCATIONS OF PANELS AND 
      SUB-PANELS READILY ACCESSIBLE (A countertop or workbench directly in front 
      of panel makes it not readily accessible. A shorter person won't be able 
      to reach and shut-off a breaker in an emergency.)  Comments: INSPECTED  | 
| 8.9 | IS THERE ONLY ONE WIRE TO 
      EACH SERVICE ENTRY CABLE LUG IN MAIN PANEL (This is where the cable from 
      meter connects into panel. Other wires, called illegal taps, on these two 
      lugs are left without overcurrent protection. Don't confuse an illegal tap 
      with surge-protection wiring where two small wires feed into main lugs and 
      go to a small lightning-surge arrestor.)  Comments: INSPECTED  | 
| 8.10 | IS THERE ONLY ONE WIRE TO 
      EACH BREAKER SCREW, NEUTRAL OR GROUND BUS SCREW, OR FUSE (Multiple wires 
      are a sign of an overloaded panel and are dangerous because the wires can 
      work loose from vibration and become a fire hazard. There is an exception 
      to the rule: Square D, type-QO, size 15, 20, 30 amp breakers are listed 
      for up to two 10 gauge wires.)  Comments: INSPECTED  | 
| 8.11 | ARE ALL WIRES TO EACH FUSE OR 
      CIRCUIT BREAKER SIZED PROPERLY (This occurs if undersize wire is used with 
      oversize breakers or fuses. This is critical so that whatever load is 
      connected to the circuit breaker will be properly protected.) 
       Comments: INSPECTED  | 
| 8.12 | ARE ALL WIRES ON 15 0R 20 AMP 
      CIRCUITS COPPER AND NOT SINGLE STRAND ALUMINUM (Aluminum wired homes built 
      from 1965 to 1972 have had numerous problems with electrical connections 
      to receptacles and switches.)  Comments: INSPECTED  | 
| 8.13 | IS PANEL FREE OF ANY WATER 
      DAMAGE (The signs of moisture damage are brown iron stains and white 
      corrosion on breakers and hot tabs inside panel.)  Comments: INSPECTED  | 
| 8.14 | IS PANEL FREE OF ANY 
      DETERIORATION (Visible condition looking for signs of arcing, burn marks, 
      blistering, or discoloration. If breaker wire connection has overheated, 
      usually because it became loose, there will be discolored or burned 
      insulation.)  Comments: INSPECTED  | 
| 8.15 | ARE SUB-PANEL GROUNDS 
      ISOLATED FROM NEUTRALS (A sub-panels most common use is to provide a 
      secondary panel some distance from the main service panel. In any 
      sub-panel, grounds and neutrals must be kept separate from each 
      other.)  Comments: INSPECTED  | 
| 8.16 | ARE APPROPRIATE OUTLETS GFCI 
      PROTECTED (A Ground Fault Circuit Interrupter is a safety device that 
      senses any shock hazard and interrupts the flow of electricity in the 
      circuit. Receptacles requiring GFCIs are bathrooms, kitchen countertops, 
      wet bar sinks, garages, pools, spa lights, and any outdoors below 
      6'6".)  Comments: INSPECTED  | 
| 8.17 | WERE A REPRESENTATIVE NUMBER 
      OF OUTLETS TESTED (Verify proper outlet operation with a Suretest tester 
      that tests for proper wiring, reversed polarity, voltage drop, ground 
      impedance, Ground-to-Neutral voltage, line voltage, high resistance 
      grounds, and false or bootleg grounds. The tester also verifies GFCI, 
      ground fault circuit interrupter type outlets.  Comments: INSPECTED  | 
| HEAT FOR: APARTMENT  | 
    LOCATION: BOTTOM UNITS IN CRAWLSPACE TOP UNITS IN WALL OR CLOSET  | 
    FUEL SOURCE: NATURAL GAS  | 
| HEAT TYPE: FORCED AIR FLOOR FURNACE FORCED AIR WALL FURNACE  | 
    IGNITION SYSTEM: MANUAL LIT STANDING PILOT LIGHT  | 
    BTU RANGE: 45000 - 50000 BTU/HR  | 
| 9.0 | INSTALLED HEATING EQUIPMENT 
      (Visible condition and check presence of conditioned air source in all 
      rooms, furnace blower free of any excess noise or vibration, and return 
      air filter is present and clean.)  Comments: INSPECTED  | 
| 9.1 | FLUE PIPE AND VENTING 
      (Visible condition checking pipe rise, diameter, junction fit, screws, and 
      clearances. A properly vented gas system exhausts combustion products to 
      exterior and provides adequate oxygen for combustion.)  Comments: INSPECTED  | 
| 9.2 | COMBUSTION AIR SUPPLY 
      (Combustion is a chemical reaction that occurs when fuel gases combine 
      with oxygen and ignite. Visual inspection of flame characteristics is a 
      good indicator of air/gas mixture problems that cause incomplete 
      combustion.)  Comments: INSPECTED  | 
| 9.3 | WAS HEAT EXCHANGER TEST 
      PROCEDURE DONE (This procedure ONLY applies to forced-air gas furnaces 
      that use a blower to distribute heat. Procedure: Check the flame with 
      blower off, then with blower on. If the main burner characteristics were 
      normal with the blower off, but change or the flame lifts from the burner 
      ports, the heat exchanger MAY be faulty.)  Comments: INSPECTED  | 
| 9.4 | WAS GAS FURNACE AREA CHECKED 
      WITH SNIFFER AND FOUND FREE OF LEAKS  Comments: INSPECTED  | 
| 9.5 | WAS A TEMPERATURE MEASURED AT 
      SUPPLY AND RETURN (Typical furnace operating temperatures are: NATURAL 
      GAS: 130-140 degrees, OIL/PROPANE: 125-135 degrees, ELECTRIC: 110-120 
      degrees, HEAT PUMP: 95-100 degrees.)  Comments: INSPECTED  | 
| 9.6 | DISTRIBUTION SYSTEMS (Visible 
      condition, checking fans, pumps, ducts and piping, insulation, air 
      filters, registers, radiators, fan coil units and convectors) 
       Comments: INSPECTED  | 
| 9.7 | THERMOSTAT (Visible 
      condition, checking if, level on wall, loose, equipment turns on/off from 
      thermostat controls.)  Comments: INSPECTED  | 
| COOLING FOR: APARTMENT  | 
    COOLING INFO: 1 WINDOW UNIT PER UNIT  | 
    NUMBER OF TONS: 2  | 
| 10.0 | INSTALLED COOLING EQUIPMENT 
      (Visible condition, checking condenser and evaporator units are free of 
      any excess noise and vibration, condenser unit free of overgrowth, coil 
      blockage, and sitting level on a slab.)  Comments: INSPECTED  | 
| 10.1 | WAS TEMPERATURE DROP 
      MEASUREMENT TAKEN FROM SUPPLY AND RETURN VENTS (A low drop could indicate 
      low Freon charge. A high drop could indicate a dirty coil, filter or 
      blower. There are other reasons why the temperature drop is out of range 
      such as thermostat calibration and humidity.)  Comments: INSPECTED  | 
| 10.2 | IS COOLING UNIT ADEQUATE FOR 
      SIZE OF HOUSE (The general rule of thumb is 1 ton for every 550 square 
      feet of living space.)  Comments: INSPECTED  | 
| FOUNDATION 
      INFORMATION: FULL CRAWLSPACE  | 
    CEILING STRUCTURE: 2 X 8 WOOD FLOOR JOISTS 1 X 8 DECKING BOARDS  | 
    FLOOR JOIST SPACING: 16 INCHES  | 
| FOUNDATION: CONCRETE BLOCK PIERS  | 
    CRAWLSPACE FLOOR: DIRT NO PLASTIC VAPOR BARRIER  | 
    METHOD USED TO OBSERVE 
      CRAWLSPACE: CRAWLED  | 
| CRAWLSPACE INFO: 2 CENTRAL FLOOR FURNACES  | 
| 11.0 | COMMON CRAWLSPACE, FOUNDATION 
      INTERIOR 
 1-All concrete block foundation walls and piers appeared relatively level and free of visible cracks and deterioration. This is good! All distribution from the meter to the unit has been replaced with PVC piping that runs on top of the crawlspace ground.  | 
| 11.1 | COMMON CRAWLSPACE, FOUNDATION 
      INTERIOR 
 1-Unit 1 still has a central floor furnace. The floor furnace for unit 2 has been removed. Refer to section 5 for further details.  | 
| 11.2 | COMMON CRAWLSPACE, FOUNDATION 
      INTERIOR 
 1,2,3,4,5,6,7,8,9,10,11,12,13,14-The majority of the wood members within crawlspace were relatively free of moisture discoloration and deterioration. Some areas around the plumbing fixtures located under the bathrooms and kitchen are moisture discolored. These were poked and the majority were found to still be structurally adequate.  | 
| 11.3 | CRAWLSPACE (Visible condition 
      of girders, piers, columns, supports, foundation walls, floor joists, 
      decking and wood members, exposed wiring and plumbing. Check that all wood 
      is free of visible contact with dirt, there is a vapor barrier covering 
      dirt floor, and crawlspace is free of visible water and debris and all 
      areas are accessible.)  Comments: INSPECTED  | 
| 11.4 | CRAWLSPACE (Visible condition 
      and operation of entry hatches and vents. Check for missing and damaged 
      vent screens that keep animals out of crawlspace.)  Comments: INSPECTED  | 
| 11.5 | ARE ALL CRAWLSPACE AREAS DRY 
      AND NOT WET OR UNUSUALLY DAMP (Crawlspace is inherently damp even though 
      there are no problems with water seepage. It is a result of the capillary 
      rise of ground moisture which can be reduced by covering the ground with a 
      plastic vapor barrier and having adequate crawlspace ventilation) 
       Comments: INSPECTED  | 
| 11.6 | ARE BASEMENT OR CRAWLSPACE 
      ELECTRICAL OUTLETS GFCI PROTECTED  Comments: INSPECTED  | 
| 11.7 | ARE MASONRY SURFACES FREE OF 
      EFFLORESCENCE DEPOSITS (These are mineral salts in the masonry that 
      dissolve in water as it passes through walls and floors. After the water 
      evaporates from the surface, it deposits these white salts. A thick layer 
      of efflorescence is an indication of considerable seepage.) 
       Comments: INSPECTED  | 
| 11.8 | ARE FOUNDATION WALLS/FLOORS 
      FREE OF VISIBLE HORIZONTAL CRACKS, V-CRACKS, OR CRACKS 1/4 INCH OR 
      LARGER(Horizontal cracks in concrete, brick, or sheetrock could indicate 
      foundation or structural problems. V-cracks are cracks that are much wider 
      at the top than the bottom and indicate possible settlement 
      problems.)  Comments: INSPECTED  | 
| 11.9 | IS CONCRETE FREE OF SHRINKAGE 
      OR HAIRLINE CRACKS (These type cracks are normal, cosmetic, usually not 
      serious and may have been caused from original concrete mix problems or 
      from settlement after house was constructed. Most likely there should not 
      be a problem, if the cracks have not worsened with time.)  Comments: INSPECTED  |